Easy Heating Engineer

Fast Heat Loss — Guide

← Back to the tool

This tool gives a quick whole-house heat loss estimate — enough to gauge the size of heat generator a property needs, in a couple of minutes on your phone. This guide explains how it works, how to read the numbers, and how to spot a building's construction.

⚠ Read this first

The tool fills in as-built construction from the age you pick. If the house has been upgraded — new windows, loft insulation topped up, cavity filled, walls or floor insulated — you must change those inputs, or the heat loss will read too high. A retrofitted house loses much less than its original fabric suggests.

Using the tool

Enter five things: postcode (sets your design temperatures), building type, storeys, floor area, and age. The moment you pick an age, the tool fills the wall, floor, loft and glazing with the construction typical for that era — shown in orange. Change anything you know is different.

If you change a wall or floor to something unusual for the age, a note appears under that section:

The two results

The tool shows two figures:

Heat loss — heat generator (the main number)

The peak heat the building loses on the coldest design day for your area (inside 21°C, outside your local design temperature). This is what you size the heat generator against — boiler, heat pump or hybrid.

Typical load

The heat loss on an average day (inside 21°C, outside the yearly-average "reference" temperature — far milder than the design day). The generator must be able to modulate down to roughly this in heating mode, or it short-cycles: firing, overshooting and switching off again and again. This matters for combi boilers and heat pumps alike.

How the HTC method works

The tool uses the Heat Transfer Coefficient (HTC) — the watts a building loses for every 1°C difference between inside and outside. Heat loss is then simply:

Heat loss = HTC × (inside temperature − outside temperature)

The HTC itself is built up from:

Tap the HTC line in the tool to see the full breakdown — each element's U-value and the watts it accounts for.

Worked example

64 m² detached bungalow, Colchester, built 2007, filled cavity, insulated solid floor, 270 mm loft, modern double glazing.

The tool builds an HTC of 117 W/°C. At the design temperature difference (21°C inside, −2.6°C outside = 23.6°C):

117 × 23.6 = 2,760 W ≈ 2.8 kW

That's the heat generator size. The typical load (at the milder reference temperature) works out around 1.3 kW — the figure the generator must be able to modulate down to.

Reading it as W/m²

The tool also shows the heat loss per square metre of floor: 2,760 W ÷ 64 m² = 43 W/m². This is a quick reference figure — a well-insulated modern home sits around 40–50 W/m², an older uninsulated one can be 100+ W/m². Bigger homes tend to show a lower W/m² (as footprint grows, wall area grows more slowly than floor area, so there's proportionally less external surface per m² of floor) — though it depends on the building's shape. Compare like-for-like sizes.

Houses with extensions

An extension is often built to a different (usually higher) standard than the original house — a 1930s house with a 2015 extension is really two fabric ages in one building. This whole-house tool works from a single age and fabric, so handle an extension one of two ways:

Either way, a full room-by-room calculation handles mixed-age fabric properly, room by room — another reason it's the right tool for designing a new system rather than just gauging generator size.

Reading a building's walls

The biggest single input is the wall type. You can often read it straight off the brickwork:

Common brick bonds

Common brick bonds. A cavity wall (stretcher bond) shows only long brick faces — the cross-sections show an open cavity and a filled one side by side. Solid walls (Flemish or English bond) show a regular pattern of short brick ends (headers), because the bricks tie the wall's full thickness together.

Blown cavity infill drill-hole evidence

Evidence of retrofit blown cavity insulation: the regular grid of filled drill-holes in the mortar is what you'll actually see on site once the work is done.

Has the cavity been filled?

Around 20 million UK homes built since 1920 have cavity walls; roughly two-thirds are now insulated, so filling is common — but far from universal. If you're not sure, choose unfilled: it's the safer assumption (higher heat loss) and errs toward not undersizing.

Method & sources

Fabric U-values come from RdSAP 10 — the standard age-and-construction defaults, so no intrusive survey is needed. Design and reference temperatures come from CIBSE 2025 Weather Data (Table 2-3), matched to your postcode across 28 UK zones. The default is the 99th percentile, which CIBSE recommends for most UK homes; the 99.6th percentile is reserved for exposed locations — though CIBSE notes the final choice is a judgement to agree between designer, client and occupier at the design stage. A toggle beneath the postcode field switches between the two. Each figure is drawn from its own authoritative source, as is standard for heat loss work.

Under Approved Document L (2026), a whole-dwelling calculation — this tool — is the appropriate method when only the heat generator is being replaced. The replacement must be sized from the calculated heat loss, not from the output of the old appliance. Fitting a new system that includes emitters needs a room-by-room calculation instead, because each room's loss sizes its own radiator or underfloor circuit.

This tool gives a whole-house estimate for heat generator replacement. Use a full room-by-room heat loss calculation when emitters are being sized.

About & Terms

Data privacy: This tool runs entirely on your device. Anything you enter stays in your device's browser storage and is not sent to any server or third party. Nothing is shared unless you choose to save and send a result yourself.

Disclaimer: This tool is provided as an estimating aid to assist competent persons in approximating a domestic building's heat loss for heat-generator sizing guidance. It is a fast whole-house estimate, not a room-by-room calculation, and does not constitute engineering certification or a substitute for professional system design, a full heat-loss calculation, or formal MCS specification. Users are responsible for verifying all figures and for ensuring all work is carried out within their demonstrated scope of competence and in accordance with current UK legislation and standards. The author accepts no liability for errors, omissions, or any loss or damage arising from use of this tool.

Source & references: U-values from RdSAP 10 (England). Design temperatures per CIBSE 2025 Weather Data. Method based on the Heat Transfer Coefficient (HTC) approach consistent with BS EN 12831-1 principles. Whole-house vs room-by-room sizing per Approved Document L Volume 1, 2026 edition, para 4.9.

© 2026 Stephen Denney. All rights reserved. May not be reproduced, redistributed, or modified without written permission.

Support & feedback

Spotted something that looks wrong, or have an idea to improve this tool? Email support → — your app build version is added automatically.